This paper describes the causes and hazards of residual current generation, designs an intelligent leakage circuit breaker, and gives the hardware structure and software design. The test results show that the intelligent circuit breaker has reliable quality and stable performance, and fully meets the requirements of national standards.
Arc-to-ground short-circuit in electrical ground faults is an important cause of electrical fires. The arc-to-ground short circuit has a large impedance and voltage drop, which limits the fault current, makes the over-current protector unable to operate or can not act in time to cut off the power supply, and the local high temperature generated by the leakage arc of several hundred milliamperes can reach 2000. Above °C, enough to ignite the surrounding combustibles and cause a fire. Moreover, the distribution of electrical equipment in all corners of the building has a wide range of hazards. If the leakage of the system is not monitored and prevented, it will pose a threat to the safety of people and property, and there is a great fire hazard. The intelligent leakage circuit breaker can accurately monitor the faults and abnormal conditions of the electric circuit, and can effectively prevent the electrical fire accidents of buildings caused by the grounding arc caused by leakage. In order to ensure the safety of people's lives and property, it is necessary to install intelligent leakage circuit breakers at the power inlet and trunk lines of buildings.
1 Reasons for residual current generation and protection principle
Let the three-phase four-wire wire pass through a zero-sequence current transformer CT together, or install a zero-sequence current transformer CT on the neutral line N, and use these CTs to detect the current vector sum of the three phases, that is, the residual current. As shown in Figure 1, according to the circuit principle, when there is no equipment leakage or ground fault in the circuit and the three-phase load is completely balanced, the vector sum of the instantaneous current in the primary side is zero, that is, Ia+Ib+Ic+IN=0 The vector sum of the magnetic flux generated in the current transformer is equal to zero, and at this time, the induced current IL=0 in the secondary coil. When the protected circuit has an insulation fault, the load side has a ground-loaded current, and the vector sum of the zero-sequence current transformer is not zero, that is, Ia+Ib+Ic+IN≠0, and the magnetic flux is generated in the current transformer. The vector sum is also not equal to zero. At this time, the induced current is generated in the secondary winding of the zero-sequence current transformer, that is, the residual current IL≠0.
The leakage circuit breaker is mainly composed of a zero sequence current transformer CT, a leakage detection circuit and a trip unit. When the protected circuit has leakage or human body electric shock, as long as the leakage or electric current reaches the leakage current value, the secondary winding of the zero-sequence current transformer outputs a signal, which is amplified by the integrated circuit amplifier and sent to the CPU, and the CPU outputs the driving signal. The leakage release action drives the circuit breaker to trip, thereby cutting off the power supply to protect against leakage and electric shock.
2 Circuit breaker controller design
2.1 Basic functions of the system
The intelligent leakage circuit breaker integrates the monitoring, analysis, alarm and control of electrical faults such as residual current, short circuit, overload, overvoltage and undervoltage (phase loss), and has the following functions:
1) With residual current detection and protection function, when the leakage current is detected, that is, the residual current IL≠0, the signal is quickly judged after sampling by the single-chip microcomputer. When the residual current reaches the setting action value, the thyristor is driven to turn on the electromagnetic The trip unit power supply, the electromagnetic trip unit pulls in, and the circuit breaker is tripped to achieve the function of leakage protection.
2) Protection action current and breaking time adjustable: When used as total protection of the station area, the residual current action value can be set to 300~1000mA, the breaking time can be set to 0.6s, and as the secondary protection, the action current can be set to 200mA file, the breaking time can be set to 0.3s. This setting can avoid the occurrence of large-scale power outage caused by over-level tripping.
3) Intelligent identification of residual current and slowly varying residual current to identify equipment leakage and live electric shock. It is an effective technical measure for rural safe electricity use to distinguish the characteristics of the rural low-voltage power grid and the wide-ranging application.
4) It has three-stage protection function of over-current long delay, short-current short-delay and short-circuit instantaneous protection, which constitutes the required protection characteristics of intelligent leakage circuit breaker. Intelligent setting of leakage current, overcurrent long delay, overcurrent short delay and overcurrent transient setting and warning value.
5) Display and store the line address, fault type, fault occurrence time, leakage current, and three-phase current value of the fault occurrence point. Up to 200 historical faults can be recorded and saved for long periods of time until they are deleted with instructions.
6) Using RS485 bus communication technology, the bus and the host can be used to form a master-slave monitoring system to realize user network connection. On one computer, 1 to 250 intelligent circuit breakers can be remotely monitored online, and the safety of each user can be checked at any time. In any case, the power supply lines of each user can be turned on or off at any time, and various parameters of the circuit breaker can be remotely set.
2.2 Overall hardware design
The intelligent leakage circuit breaker is mainly composed of power supply circuit, single chip PIC24FJ64, three-phase AC voltage and current detection circuit, residual current detection circuit, serial communication interface circuit, human-machine interface circuit and alarm, etc., as shown in Figure 2. .
Its main working principle: after the three-phase current, leakage and voltage signals obtained from the current transformer and the linear optical isolator are conditioned, input to the A/D conversion of the single-chip microcomputer, and the single-chip microcomputer samples it and analyzes it, and outputs the corresponding Display and alarm signals, etc. The result of the analysis can also be transmitted to the host computer via the RS485 bus.
2.2.1 Single chip circuit
The microcontroller uses PIC24FJ64, which is a high-performance CPU of improved Harvard architecture designed by Microchip. It is the core of intelligent circuit breaker. It completes various control functions of intelligent circuit breaker, including three-phase voltage, three-phase current and leakage. Current sampling, data processing, alarm output, communication with the host computer, liquid crystal display and buttons. Microchip's ability to develop, develop, and manufacture microcontroller technology has the following advantages: 1) Harvard bus architecture; 2) reduced instruction set (RISC) technology; 3) simple addressing; 4) high code compression; 5) high speed; 6) Power consumption is extremely low; 7) PIC16F877 chip has A/D, MSSP, USART serial bus port, etc., and has external circuit is simple, easy to develop, C language programming, program confidentiality and so on.
2.2.2 Residual current detection circuit
The residual current detection circuit is a zero sequence current transformer. The protected phase line and neutral line pass through the toroidal core to form the primary coil of the transformer. The winding wound on the toroidal core forms the secondary coil of the transformer. If no leakage occurs, then the phase line flows. The current vector sum of the neutral line is equal to zero, so the corresponding induced electromotive force cannot be generated on the secondary coil. If a leakage occurs, the current vector of the phase line and the neutral line is not equal to zero, so that the induced electromotive force is generated on the secondary coil, and this signal is sent to the intermediate link for further processing, as shown in FIG.
After the AC signal is processed by the absolute value amplifying circuit, full-wave rectification is obtained, and the processed signal is sent to the single chip microcomputer. The MCU samples 36 points per cycle, and the effective value of the residual current can be calculated according to Equation (1), where X is the sampled value.
2.2.3 Three-phase voltage and current and phase sequence detection
The current detection consists of two three-phase AC transformers, an operational amplifier and a rectification filter circuit. The three-phase AC transformer converts the current into a voltage signal, and the circuit formed by the operational amplifier is conditioned and rectified and filtered to be input to the A/D converter of the single chip microcomputer for conversion.
The traditional voltage detection method uses a voltage transformer or a linear optical isolator. The disadvantage of using a voltage transformer for voltage detection is that the transformer is bulky. In many cases, the designed product requires a small size of the controller, so that the installation and use are convenient. The disadvantage of using linear optical isolation is that the voltage detection accuracy is not high. The system uses the current transformer and the resistor in series to detect the voltage, which greatly reduces the volume of the controller and ensures the high precision of the voltage detection. The schematic diagram is shown in Figure 4.
The current transformer adopts the 1:1 current transformer TV16 produced by Yaohua Electronics. Since the primary and secondary sides of the current transformer are equal, the secondary voltage is equal to the primary voltage. By selecting the appropriate resistor R1, the peak value of the output voltage of the secondary side of the current transformer does not exceed the maximum allowable sampling voltage. The secondary voltage of the transformer becomes a single-phase full-wave after passing through the rectifier bridge. The A/D converter of the single-chip microcomputer can be fully The wave is sampled and analyzed.
The power phase sequence detection adopts the peak detection method, and the phases of the three-phase voltages of A, B, and C differ by 120°. The detection method is that when the maximum value of the phase A is detected, the timing is started, and when the maximum value of the phase B is detected, the timing is stopped, and the time interval between the peaks of the two phases of A and B can be obtained, and is set to Δt, according to △. t can find the phase difference φ of the two phases A and B, and the calculation formula is:
If the calculated phase difference is 110° ≤ φ ≤ 130°, the phase sequence is considered normal, and if it exceeds this range, it is determined that the phase sequence is wrong.
2.2.4 RS485 bus hardware circuit
The intelligent leakage circuit breaker and the upper computer use RS485 bus communication, one host can control up to 250 circuit breakers, the RS485 communication system adopts the master-slave structure, the slave does not actively send commands or data, and everything is controlled by the host. Therefore, in a communication system, only one upper computer is used as the host, and the other slaves cannot communicate with each other, and even if there is information exchange, it must be forwarded through the host. The hardware circuit for communication with the host computer is shown in Figure 5.
The communication between the intelligent circuit breaker and the host computer adopts the Modbus communication protocol. The Modbus communication protocol is one of the mainstream communication protocols commonly used by international intelligent instruments. The master-slave communication mode is adopted between the two. When the host computer sends a communication command to the circuit breaker, the slave device that meets the corresponding address code receives the communication command, and reads the information according to the function code and related requirements. If the CRC is correct, the corresponding task is executed and the execution result is returned to the host.
3 software design of intelligent circuit breaker
The software completes the function of the whole circuit breaker and adopts a modular structured C language programming scheme. Mainly included procedures:
1) System main program. Mainly complete the initialization of the system's port, timer, A / D converter and other modules, and complete the LCD interface display work.
2) The timer interrupt service subroutine and the A/D conversion subroutine mainly complete the A/D conversion task and the button processing function. The MCU needs to sample 36 times in one cycle (20ms) and save the sample summer vacation.
3) The data processing subroutine mainly performs the calculation of the leakage current, the judgment of the leakage current, and the processing of the trip or not.
4) The button processing subroutine mainly provides a man-machine dialogue channel. The user can set the leakage protection setting value, delay trip time, etc. through the button, and the parameter modification has password protection.
The main software system block diagram is shown in Figure 6.
Edit Comment: Intelligent leakage circuit breaker IRCCB is widely used in distribution network. A low-voltage electrical appliance is mainly used to prevent personal electric shock and equipment leakage fault. The correctness of its work directly affects the safety and reliability of power supply. The intelligent design of the intelligent leakage circuit breaker is reliable, the quality is reliable, the anti-interference is strong, and the system and network of the circuit breaker control can be realized through the application of the bus communication technology.
Electronic enthusiasts "Automotive Electronics Special", more quality content, download now
[GEFORCE RTX 30 SERIES]GeForce RTX 30 Series GPUs deliver the ultimate performance for gamers and creators. They`re powered by Ampere - NVIDIA`s 2nd gen RTX architecture - with new RT Cores, Tensor Cores, and streaming multiprocessors for the most realistic ray-traced graphics and cutting-edge AI features
[DLSS AI ACCELERATION]NVIDIA DLSS is groundbreaking AI rendering that boosts frame rates with uncompromised image quality using the dedicated AI processing Tensor Cores on GeForce RTX. This gives you the performance headroom to crank up settings and resolutions for an incredible visual experience. The AI revolution has come to gaming
[GRAPHENE BACKPLATE & CUTTING EDGE TRIPLE FAN THERMAL]A lightweight composite Graphene backplate reinforces the length of the graphics card while providing passive thermal conduction properties. The award-winning MSI TORX Fan 3.0 design keeps the limits of thermal performance turning. Fan blades alternate between traditional blades and dispersion blades that focus and accelerate airflow into the heatsink
[Up Your Creative Game]Take your creative projects to a new level with GeForce RTX 30 Series GPUs. Delivering AI-acceleration in top creative apps. Backed by the NVIDIA Studio platform of dedicated drivers and exclusive tools. And built to perform in record time. Whether rendering complex 3D scenes, editing 8K video, or livestreaming with the best encoding and image quality, GeForce RTX GPUs give you the performance to create your best
[Stream Like A Boss]Steal the show with incredible graphics and smooth, stutter-free livestreaming. Next-generation hardware encoding and decoding combine to show off all your best moments in exquisite detail. And the all-new NVIDIA Broadcast app takes your livestreams to the next level with powerful AI capabilities to improve audio and video quality with effects like virtual background, webcam auto frame, and microphone noise removal
best mining graphics card,best graphics card for mining,graphic card best buy,best graphics card for mining,gpu mining
Easy Electronic Technology Co.,Ltd , https://www.pcelectronicgroup.com