YDB electroscope use methods and precautions:
When using the electroscope, it must be noted that its rated voltage is compatible with the voltage level of the electrical equipment being inspected, otherwise it may endanger the personal safety of the electroscope operator or cause misjudgment. During the power inspection, the operator should wear insulated gloves and hold the handshake part below the cover guard ring. First check on the powered equipment . When checking, gradually move the electroscope closer to the live equipment until it emits light or sounds to confirm. The performance of the electroscope is intact. The electroscope with self-test system should first activate the self-test button to confirm that the electroscope is in good condition, and then on the equipment that needs to be inspected. The test should also gradually move the electroscope closer to the device under test. Until the conductive part of the device is touched, if the process is silent and light indication, the device can be judged to be uncharged. Conversely, if the device suddenly emits light or sounds during the approaching process, it is considered that the device is charged, then the approach can be stopped and the test is terminated. Electricity. In addition, the windmill type electroscope is only suitable for indoor or outdoor use in good weather. It is forbidden to use under the environmental conditions such as rain and snow.
(1) When testing with high-voltage electroscope, it is necessary to wear insulated gloves that meet the requirements; it is not allowed to be tested by one person alone, and must be monitored by others; during the test, it is necessary to prevent phase-to-phase or short-circuit to ground; human body and charged body should Maintain a sufficient safety distance, the safety distance of 10kV high voltage is 0. 7 m or more. When used outdoors, the weather must be good. In the weather with heavy rain, snow, fog and humidity, the type of ordinary insulating rod should not be used to prevent danger. .
(2) Before use, the insulation rod should be stretched to the specified length according to the voltage level of the equipment (line) to be tested. Select the appropriate type of indicator and insulation rod, check the indicator, and use the high-voltage electroscope for investment. Must be qualified by electrical test.
(3) For the rotary high-voltage electroscope, the inspected indicator should be screwed on the insulating rod before use, and the surface should be wiped clean with a silk cloth, and then rotated to the desired angle for easy observation when used.
(4) For capacitive high-voltage electroscopes, the insulation bar is marked with a red line, and the upper part of the red line indicates that there is a capacitive element inside, and it is a charged part. This part should be in accordance with the requirements of the "Electric Safety Work Regulations" and adjacent conductors or grounding bodies. Maintain the necessary safety distance.
(5) When using, special attention should be paid to the hand grip not exceeding the guard ring
(6) When using a rotary high-voltage electroscope, the metal contacts of the indicator should gradually approach the device under test (or wire). Once the indicator blade begins to rotate normally, it indicates that the device has electricity and should leave the device under test. The blades cannot be rotated for a long time to ensure the life of the electroscope. When there is a residual charge voltage on the cable or capacitor, the indicator blade will slowly turn a few turns for a short time and then stop itself, so it can accurately identify whether the device is powered off.
(7) The inspection of the line shall be carried out phase by step. When checking the circuit breaker or isolating switch or other maintenance equipment for communication, the phases shall be checked separately on both sides of the incoming and outgoing lines. When the multi-layer power line erected on the same tower is tested, the low voltage and the post-test high voltage are a priori, and the lower layer and the apostate upper layer are a priori.
(8) The power inspection on the capacitor bank should be performed after the discharge is completed.
(9) After each use, the surface dust should be wiped clean and stored in a dry and ventilated place to prevent moisture before shrinking the insulating rod and removing the turning indicator. The slewing indicator should be kept in a safe place, and it must not be strongly vibrated or impacted, nor allowed to adjust and disassemble.
(10) In order to ensure the safety of use, the electroscope should conduct a preventive electrical test every six months.